The controls and spray unit shall be within 18 inches 455 mm of the front of the shower.
Ada vertical grab bar height for showers.
A vertical grab bar 18 455 mm minimum in length mounted along the side wall.
However ada standards recommend that rear grab bars be installed at the height of between 33 and 36 inches above the finished floor of the tub shower or bathroom.
Example single user toilet room.
The icc a117 1 standard which is referenced by the international building code requires an 18 minimum vertical grab bar at transfer showers and bathtubs.
Vertical bars are helpful and provide support when stepping into bathtubs or showers.
Figure 608 3 3 grab bars for alternate roll in type showers.
The ada standards do not require a vertical grab bar at bathing fixtures.
Each grab bar shall be 24 inches 610 mm long minimum and shall be installed 24 inches 610 mm maximum from the head end wall and 12 inches 305 mm maximum from the control end wall.
The controls shall be placed in an area between 38 48 inches 965 1220 mm above the floor.
This is a good starting range.
Each grab bar shall be installed 15 inches 380 mm maximum from the head end wall and 12 inches 305 mm maximum from the control end wall.
The grab bar s shall be mounted 33 36 inches 840 915 mm above the shower floor measured at the entry.
Grab bars shall not be provided above the seat.
If the grab bar is 36 high a non recessed toilet paper dispenser located above the bar must have an outlet at exactly 48 high to accommodate both the max.
Two grab bars shall be installed on the back wall one located in accordance with 609 4 and the other located 8 inches 205 mm minimum and 10 inches 255 mm maximum above the rim of the bathtub.
A folding or non folding seat shall be provided in transfer type shower compartments.
Vertical grab bar requirements.
Call 714 500 7585 for a free quote today be very careful when it comes to the height of your grab bars in showers and toilets the top of a horizontal grab bar must be 33 36 inches off the floor.
Reach height and the 12 min.
Center line of the bar located 39 990 mm minimum and 41 1040 mm maximum from the rear wall.
The bottom of a vertical bar in transfer showers must be 3 6 inches over the horizontal bar on the wall.
Generally grab bars should be installed at whatever height is most appropriate for their primary user.